2013年1月7日星期一

AuCom Electronics CSXi IMS2


Description


CSXi compact soft starters are a comprehensive motor starting and protection solution. These compact, reliable starters provide the latest constant current start technology and robust TVR soft stop, to reduce electrical and mechanical stress on your motor. The CSXi also incorporates essential motor protection functions to safeguard your motor during operation.
The CSXi soft starter's small size and integrated bypass relays make installation easy, and allow the soft starter to fit in compact enclosures with limited ventilation. Rotary switches simplify configuration, and remote display and communication options allow trouble-free integration into common control networks.
CSXi


CSXi Family

ModelNormal DutyHeavy Duty
CSXi-00718 A17 A
CSXi-01534 A30 A
CSXi-01842 A36 A
CSXi-02248 A40 A
CSXi-03060 A49 A
CSXi-03775 A65 A
CSXi-04585 A73 A
CSXi-055100 A96 A
CSXi-075140 A120 A
CSXi-090170 A142 A
CSXi-110200 A165 A




Description

IMS2 soft starters are a total motor starting solution, combining high-level functionality with flexibility and ease of use. Whether you need a simple solution to starting or stopping your motor, or a comprehensive protection system for your motor and installation, the IMS2 can be configured to suit.
The IMS2 offers a choice of soft start and soft stop profiles to ensure optimum control for all load types. The unique torque control system gives more linear acceleration than standard constant current, and a special pump control function reduces water hammer. The IMS2 also incorporates advanced motor and load protection features, ensuring safer operation for your application. With extensive input/output and integration options, the IMS2 minimises installation time and costs and ensures that motors can be operated with confidence.
In simple installations, set up is very quick as only one parameter needs to be set before the starter is ready to use. For advanced applications, an extensive range of functions allows you to use the IMS2 to suit nearly all motor starting and control requirements.
IMS2 soft starters can be connected in in-line or inside delta configuration. Inside delta connection allows control of motors 50% larger than the standard rating, and also allows replacement of star/delta starters without changing existing motor wiring. Power connections on 302 ~ 1574 A models can be configured for any combination of top or bottom input and output, making the IMS2 ideal for integration into existing installations.

 IMS2
IMS2

Specifications

Supply 
Mains Voltage 
IMS2xxxx-V5
3 x 200 VAC ~ 525 VAC (in-line/3 wire connection)
3 x 200 VAC ~ 440 VAC (inside delta/6 wire connection)
IMS2xxxx-V7
3 x 200 VAC ~ 690 VAC (in-line/3 wire connection)
3 x 200 VAC ~ 440 VAC (inside delta/6 wire connection)
Control Voltage 
    IMS2xxxx-xx-C12110 VAC or 230 VAC (+10%/-15%)
    IMS2xxxx-xx-C24230 VAC or 400 VAC (+10%/-15%)
    IMS2xxxx-xx-C45460 VAC or 575 VAC (+10%/-15%)
Mains frequency 
    at start50 Hz (+/- 2 Hz) or 60 Hz (+/- 2 Hz)
    during start> 45 Hz (50 Hz supply) or > 55 Hz (60 Hz supply)
    during run> 48 Hz (50 Hz supply) or > 58 Hz (60 Hz supply)
Control Inputs 
Start (Terminals C23, C24)Active 24 VDC, 8 mA approx
Stop (Terminals C31, C32)Active 24 VDC, 8 mA approx
Reset (Terminals C41, C42)Active 24 VDC, 8 mA approx
Programmable Input A (Terminals C53, C54)Active 24 VDC, 8 mA approx
Outputs 
Relay Outputs5 A @ 30 VDC or 250 VAC resistive
 360 VA inductive
Run Output (Terminals 23, 24)Normally Open
Programmable Relay Output A (Terminals 13, 14)Normally Open
Programmable Relay Output B (Terminals 33, 34)Normally Open
Programmable Relay Output C (Terminals 41, 42, 44)Changeover
Analogue Output (Terminals B10, B11)4-20 mA (maximum burden 500 W)
Sundry 
Enclosure rating
    IMS2xxxx-xx-xxx-xx-E0IP00 (open chassis)
    IMS2xxxx-xx-xxx-xx-E4IP42
    IMS2xxxx-xx-xxx-xx-E5IP54
Rated short circuit current IMS20018 ~ IMS2089742 kA
Rated insulation voltage690 V
Surges2 kV line to earth, 1 kV line to line
Fast transients2 kV / 5 kHz
Form designationForm 1
Electrostatic discharge4 kV contact discharge, 8 kV air discharge
Equipment class (EMC)Class A
Radio-frequency electromagnetic field0.15 MHz – 80 MHz: 140 dBµV
 80 MHz – 1 GHz: 10 V/m
Pollution degreePollution Degree 3
Operating temperatures- 5 °C ~ + 60 °C
Relative humidity5% ~ 95% (max non-condensing)
Standards Approvals 
CEIEC 60947-4-2
UL and C-ULUL 508
C-tickIEC 60947-4-2