Description
CSXi compact soft starters are a comprehensive motor starting and protection solution. These compact, reliable starters provide the latest constant current start technology and robust TVR soft stop, to reduce electrical and mechanical stress on your motor. The CSXi also incorporates essential motor protection functions to safeguard your motor during operation.
The CSXi soft starter's small size and integrated bypass relays make installation easy, and allow the soft starter to fit in compact enclosures with limited ventilation. Rotary switches simplify configuration, and remote display and communication options allow trouble-free integration into common control networks.
CSXi Family
Model | Normal Duty | Heavy Duty |
CSXi-007 | 18 A | 17 A |
CSXi-015 | 34 A | 30 A |
CSXi-018 | 42 A | 36 A |
CSXi-022 | 48 A | 40 A |
CSXi-030 | 60 A | 49 A |
CSXi-037 | 75 A | 65 A |
CSXi-045 | 85 A | 73 A |
CSXi-055 | 100 A | 96 A |
CSXi-075 | 140 A | 120 A |
CSXi-090 | 170 A | 142 A |
CSXi-110 | 200 A | 165 A |
Description
IMS2 soft starters are a total motor starting solution, combining high-level functionality with flexibility and ease of use. Whether you need a simple solution to starting or stopping your motor, or a comprehensive protection system for your motor and installation, the IMS2 can be configured to suit.
The IMS2 offers a choice of soft start and soft stop profiles to ensure optimum control for all load types. The unique torque control system gives more linear acceleration than standard constant current, and a special pump control function reduces water hammer. The IMS2 also incorporates advanced motor and load protection features, ensuring safer operation for your application. With extensive input/output and integration options, the IMS2 minimises installation time and costs and ensures that motors can be operated with confidence.
In simple installations, set up is very quick as only one parameter needs to be set before the starter is ready to use. For advanced applications, an extensive range of functions allows you to use the IMS2 to suit nearly all motor starting and control requirements.
IMS2 soft starters can be connected in in-line or inside delta configuration. Inside delta connection allows control of motors 50% larger than the standard rating, and also allows replacement of star/delta starters without changing existing motor wiring. Power connections on 302 ~ 1574 A models can be configured for any combination of top or bottom input and output, making the IMS2 ideal for integration into existing installations.
Specifications
Supply | |
Mains Voltage | |
IMS2xxxx-V5
| 3 x 200 VAC ~ 525 VAC (in-line/3 wire connection) |
3 x 200 VAC ~ 440 VAC (inside delta/6 wire connection) | |
IMS2xxxx-V7
| 3 x 200 VAC ~ 690 VAC (in-line/3 wire connection) |
3 x 200 VAC ~ 440 VAC (inside delta/6 wire connection) | |
Control Voltage | |
IMS2xxxx-xx-C12 | 110 VAC or 230 VAC (+10%/-15%) |
IMS2xxxx-xx-C24 | 230 VAC or 400 VAC (+10%/-15%) |
IMS2xxxx-xx-C45 | 460 VAC or 575 VAC (+10%/-15%) |
Mains frequency | |
at start | 50 Hz (+/- 2 Hz) or 60 Hz (+/- 2 Hz) |
during start | > 45 Hz (50 Hz supply) or > 55 Hz (60 Hz supply) |
during run | > 48 Hz (50 Hz supply) or > 58 Hz (60 Hz supply) |
Control Inputs | |
Start (Terminals C23, C24) | Active 24 VDC, 8 mA approx |
Stop (Terminals C31, C32) | Active 24 VDC, 8 mA approx |
Reset (Terminals C41, C42) | Active 24 VDC, 8 mA approx |
Programmable Input A (Terminals C53, C54) | Active 24 VDC, 8 mA approx |
Outputs | |
Relay Outputs | 5 A @ 30 VDC or 250 VAC resistive |
360 VA inductive | |
Run Output (Terminals 23, 24) | Normally Open |
Programmable Relay Output A (Terminals 13, 14) | Normally Open |
Programmable Relay Output B (Terminals 33, 34) | Normally Open |
Programmable Relay Output C (Terminals 41, 42, 44) | Changeover |
Analogue Output (Terminals B10, B11) | 4-20 mA (maximum burden 500 W) |
Sundry | |
Enclosure rating | |
IMS2xxxx-xx-xxx-xx-E0 | IP00 (open chassis) |
IMS2xxxx-xx-xxx-xx-E4 | IP42 |
IMS2xxxx-xx-xxx-xx-E5 | IP54 |
Rated short circuit current IMS20018 ~ IMS20897 | 42 kA |
Rated insulation voltage | 690 V |
Surges | 2 kV line to earth, 1 kV line to line |
Fast transients | 2 kV / 5 kHz |
Form designation | Form 1 |
Electrostatic discharge | 4 kV contact discharge, 8 kV air discharge |
Equipment class (EMC) | Class A |
Radio-frequency electromagnetic field | 0.15 MHz – 80 MHz: 140 dBµV |
80 MHz – 1 GHz: 10 V/m | |
Pollution degree | Pollution Degree 3 |
Operating temperatures | - 5 °C ~ + 60 °C |
Relative humidity | 5% ~ 95% (max non-condensing) |
Standards Approvals | |
CE | IEC 60947-4-2 |
UL and C-UL | UL 508 |
C-tick | IEC 60947-4-2 |
没有评论: