Frequency Inverter, AC Drive, Variable Speed Drive, Adjustable Speed Drive, Frequency Converter, VFD, VSD, Adjustable Frequency Drive, AFD, ASD, AC Motor Drive, Frequency Changers, Inverter, Biến tần, frequenzwandler, Azionamenti, Преобразователи частоты, приводов переменного тока, falowniki, frequentie regelaars, frequentieregelaars, convertisseur frequence, variateur frequence, Frequenzumrichter, convertitore frequenza, Inversores Frequência, ווסתי מהירות, محول تردد, اینورتر, Vectör Sürücüler
2012年11月23日星期五
VTdrive VFD solutions
Auto tuning
◆ First step, must disconnected from the load. If the motor can be disconnected
from the load, it can select rotation auto-tuning (P9.15=2), or it can select
static auto-tuning only.
◆ If the inverter power does not match the motor power, select static
auto-tuning. after the tuning, manually change the no load current P9.05 to
about 40% of the motor rated current P9.04
◆ Setting P0.01=5,recover parameter to factory setting
◆ Setting motor basic frequency P0.15 according to motor nameplate
◆ Setting motor rated voltage P0.12 according to motor nameplate
◆ Setting motor pole P9.01 according to motor nameplate
◆ Setting motor rated rotation P9.02 according to motor nameplate
◆ Setting motor rated power P9.03 according to motor nameplate
◆ Setting motor rated current P9.04 according to motor nameplate
◆ Setting P9.15=1 and pressure RUN key to perform static auto-tuning
◆ Setting P9.15=2 and pressure RUN key to perform static rotating-tuning, if
perform rotating-tuning, should be careful because the motor will be run after
pressure RUN key.
◆ After auto-tuning, the motor will stop auto.Solutions